35 changes: 35 additions & 0 deletions docs/design-basis.md
Original file line number Diff line number Diff line change
@@ -0,0 +1,35 @@
# Design basis

Every value in kitlist's equipment libraries traces to a cited source, so any
standard size can be checked against the document it came from.

## How sources are recorded

- Each library CSV in `src/kitlist/data/library/` has a `source` column holding a
reference ID from the table below.
- A test fails if a library uses an ID that isn't listed here, so no value can be
added without a source.
- Paywalled standards are cited by edition and clause. Their text is not reproduced.

## References

| ID | Document | Used for | Verified | Notes |
|---|---|---|---|---|
| DOE-431.196a | US 10 CFR 431.196(a)(2), low-voltage dry-type distribution transformers, table for units made 2016–2029 | `ieee-dry` kVA ratings | Against the regulation text, 2026-11-08 | Applies legally to 60 Hz units sold in the US; cited as a public record of the North American rating series. Free at ecfr.gov. |
| DOE-431.196b | US 10 CFR 431.196(b)(2), liquid-immersed distribution transformers, Table 5 | `ieee-pad` kVA ratings, limited to the scope of IEEE-C57.12.38 (single-phase, ≤ 250 kVA) and IEEE-C57.12.34 (three-phase) | Against the regulation text, 2026-11-08 | Same note as above. |
| IEC-60076-1 | IEC 60076-1:2011, Power transformers – Part 1: General, clause 5.1.2 (preferred values of rated power, R10 series of ISO 3) | `iec` kVA ratings | **No** | Values are the R10 preferred numbers. Paywalled; verify against a copy before relying on this family. |
| IEEE-C57.12.38 | IEEE C57.12.38-2025, pad-mounted, self-cooled, single-phase distribution transformers, 250 kVA and smaller | Scope of `ieee-pad` single-phase | Scope only, from the published abstract | Scope is 60 Hz; on 50 Hz projects, specify "in general accordance with, except 50 Hz". Paywalled. |
| IEEE-C57.12.34 | IEEE C57.12.34-2022, pad-mounted, compartmental-type, self-cooled, three-phase distribution transformers, 10 MVA and smaller | Scope of `ieee-pad` three-phase | Scope only, from the published abstract | Same note. Paywalled. |

## Transformers

Library: `transformer_kva.csv`, one row per standard rating, tagged by family (D7):

- `ieee-dry`: low-voltage dry-type, North American series (DOE-431.196a).
- `ieee-pad`: liquid-filled padmount, North American series (DOE-431.196b), within the
scope of IEEE C57.12.38 (single-phase) and C57.12.34 (three-phase).
- `iec`: IEC series (IEC-60076-1). Not yet verified against the standard.

These are *standard* ratings. Sizes local suppliers rarely stock (for example
10 kVA single-phase padmounts or 31.5 kVA IEC units) are still listed; trimming the
list to what is buyable is a separate, project-level decision.
2 changes: 2 additions & 0 deletions docs/requirements.md
Original file line number Diff line number Diff line change
Expand Up @@ -32,12 +32,14 @@ it exists.
| NFR-02 | The workbook is self-contained: no links to other files. |
| NFR-03 | Every engineering rule has Python tests, and an automated test checks the Excel formula agrees with Python (ADR 0002). |
| NFR-04 | A schedule shows what a drawing needs: at most about 7 ratings per type. Detail belongs in the specification. |
| NFR-05 | Every value in an equipment library cites a source listed in `docs/design-basis.md`. A test fails if a source is missing or unlisted. |

## Non-goals (v0.1)

- Writing specifications.
- A manufacturer product database. Libraries hold standard sizes and typical dimensions only.
- Load calculations. Demand is an input, calculated elsewhere.
- Certifying compliance with standards. Library sizes come from the cited standards; whether a product complies is confirmed by the manufacturer's data.
- DXF/PDF output, AutoCAD Data Link and native AutoCAD table objects. v0.1 gets schedules into drawings by copy-paste; the rest comes later.

## Decisions
Expand Down
65 changes: 65 additions & 0 deletions src/kitlist/data/library/transformer_kva.csv
Original file line number Diff line number Diff line change
@@ -0,0 +1,65 @@
family,phase,kva,source
ieee-dry,1,15,DOE-431.196a
ieee-dry,1,25,DOE-431.196a
ieee-dry,1,37.5,DOE-431.196a
ieee-dry,1,50,DOE-431.196a
ieee-dry,1,75,DOE-431.196a
ieee-dry,1,100,DOE-431.196a
ieee-dry,1,167,DOE-431.196a
ieee-dry,1,250,DOE-431.196a
ieee-dry,1,333,DOE-431.196a
ieee-dry,3,15,DOE-431.196a
ieee-dry,3,30,DOE-431.196a
ieee-dry,3,45,DOE-431.196a
ieee-dry,3,75,DOE-431.196a
ieee-dry,3,112.5,DOE-431.196a
ieee-dry,3,150,DOE-431.196a
ieee-dry,3,225,DOE-431.196a
ieee-dry,3,300,DOE-431.196a
ieee-dry,3,500,DOE-431.196a
ieee-dry,3,750,DOE-431.196a
ieee-dry,3,1000,DOE-431.196a
ieee-pad,1,10,DOE-431.196b
ieee-pad,1,15,DOE-431.196b
ieee-pad,1,25,DOE-431.196b
ieee-pad,1,37.5,DOE-431.196b
ieee-pad,1,50,DOE-431.196b
ieee-pad,1,75,DOE-431.196b
ieee-pad,1,100,DOE-431.196b
ieee-pad,1,167,DOE-431.196b
ieee-pad,1,250,DOE-431.196b
ieee-pad,3,15,DOE-431.196b
ieee-pad,3,30,DOE-431.196b
ieee-pad,3,45,DOE-431.196b
ieee-pad,3,75,DOE-431.196b
ieee-pad,3,112.5,DOE-431.196b
ieee-pad,3,150,DOE-431.196b
ieee-pad,3,225,DOE-431.196b
ieee-pad,3,300,DOE-431.196b
ieee-pad,3,500,DOE-431.196b
ieee-pad,3,750,DOE-431.196b
ieee-pad,3,1000,DOE-431.196b
ieee-pad,3,1500,DOE-431.196b
ieee-pad,3,2000,DOE-431.196b
ieee-pad,3,2500,DOE-431.196b
iec,3,25,IEC-60076-1
iec,3,31.5,IEC-60076-1
iec,3,40,IEC-60076-1
iec,3,50,IEC-60076-1
iec,3,63,IEC-60076-1
iec,3,80,IEC-60076-1
iec,3,100,IEC-60076-1
iec,3,125,IEC-60076-1
iec,3,160,IEC-60076-1
iec,3,200,IEC-60076-1
iec,3,250,IEC-60076-1
iec,3,315,IEC-60076-1
iec,3,400,IEC-60076-1
iec,3,500,IEC-60076-1
iec,3,630,IEC-60076-1
iec,3,800,IEC-60076-1
iec,3,1000,IEC-60076-1
iec,3,1250,IEC-60076-1
iec,3,1600,IEC-60076-1
iec,3,2000,IEC-60076-1
iec,3,2500,IEC-60076-1
38 changes: 38 additions & 0 deletions src/kitlist/library.py
Original file line number Diff line number Diff line change
@@ -0,0 +1,38 @@
"""Equipment libraries: standard sizes read from the CSV files in data/library/.

Every row cites a source listed in docs/design-basis.md (NFR-05).
"""

import csv
from dataclasses import dataclass
from importlib.resources import files

FAMILIES = ("ieee-dry", "ieee-pad", "iec") # transformer rating families (D7)


@dataclass(frozen=True)
class TransformerRating:
"""One row of transformer_kva.csv."""

family: str
phase: int
kva: float
source: str


def transformer_ratings() -> list[TransformerRating]:
"""Every standard transformer rating in the library."""
path = files("kitlist").joinpath("data/library/transformer_kva.csv")
# "utf-8-sig" also accepts the invisible marker Excel adds when it saves a CSV.
text = path.read_text(encoding="utf-8-sig")
return [
TransformerRating(row["family"], int(row["phase"]), float(row["kva"]), row["source"])
for row in csv.DictReader(text.splitlines())
]


def transformer_sizes(family: str, phase: int) -> list[float]:
"""Standard kVA sizes for one family and phase count, smallest first."""
if family not in FAMILIES:
raise ValueError(f"unknown transformer family '{family}'; expected one of {FAMILIES}")
return sorted(r.kva for r in transformer_ratings() if r.family == family and r.phase == phase)
73 changes: 73 additions & 0 deletions tests/test_library.py
Original file line number Diff line number Diff line change
@@ -0,0 +1,73 @@
"""Tests for the equipment libraries (NFR-05, REQ-11)."""

from pathlib import Path

import pytest

from kitlist.library import FAMILIES, transformer_ratings, transformer_sizes

DESIGN_BASIS = Path(__file__).parents[1] / "docs" / "design-basis.md"
RATINGS = transformer_ratings()


def reference_ids() -> set[str]:
"""The IDs in the first column of the References table in docs/design-basis.md."""
text = DESIGN_BASIS.read_text(encoding="utf-8")
references = text.split("## References")[1].split("\n## ")[0]
ids = set()
for line in references.splitlines():
if not line.startswith("|"):
continue
first_cell = line.split("|")[1].strip()
if first_cell != "ID" and not first_cell.startswith("---"):
ids.add(first_cell)
return ids


# ---- traceability (NFR-05) ----


def test_reference_table_can_be_read():
# Checks the helper above: if this fails, the other tests can't be trusted.
assert {"DOE-431.196a", "DOE-431.196b", "IEC-60076-1"} <= reference_ids()


def test_every_rating_cites_a_source_listed_in_the_design_basis():
missing = {r.source for r in RATINGS} - reference_ids()
assert not missing, f"not listed in docs/design-basis.md: {sorted(missing)}"


# ---- families (REQ-11, D7) ----


def test_every_rating_belongs_to_a_known_family():
unknown = {r.family for r in RATINGS} - set(FAMILIES)
assert not unknown, f"unknown families: {sorted(unknown)}"


def test_families_are_never_mixed():
# 25 kVA three-phase is an IEC rating, not a North American one
assert 25 in transformer_sizes("iec", phase=3)
assert 25 not in transformer_sizes("ieee-dry", phase=3)


def test_unknown_family_is_an_error():
with pytest.raises(ValueError, match="unknown transformer family"):
transformer_sizes("ansi", phase=3)


# ---- library contents ----


def test_no_rating_is_listed_twice():
keys = [(r.family, r.phase, r.kva) for r in RATINGS]
assert len(keys) == len(set(keys))


def test_sizes_come_back_smallest_first():
sizes = transformer_sizes("ieee-dry", phase=3)
assert sizes == sorted(sizes)


def test_single_phase_padmounts_stay_within_c57_12_38_scope():
assert max(transformer_sizes("ieee-pad", phase=1)) <= 250