Distrust stale current readings; measure runtime from flow - #86
Merged
Merged
Conversation
An ESPHome sensor keeps serving its last value indefinitely once its source stops responding, and nothing downstream can tell the difference. On two consecutive mornings the PZEM stopped returning valid Modbus frames for exactly the hour both pumps ran (04:00-05:00), and because its readings froze rather than disappearing, everything believed them: Pump No Current reported a fault for a solid hour while the pump was drawing ~1500 W, runtime stopped accumulating for a pump that was running, and when the frames came back at 05:00:02 the current sensor jumped from a frozen value to a live one in a single sample — spiking the spread estimate past the variance threshold and setting the anomaly flag chattering 285 times. The energy registers appeared to dump a whole hour at once for the same reason: the meter had been counting internally all along, only the reads were dead. The device never disconnected and the recorder was healthy throughout, so the only signal that could have distinguished a live reading from a frozen one was when it last arrived. Nothing was tracking that. This does not fix the underlying dropout, which is still unexplained and most likely electrical. It stops the controller drawing false conclusions from dead data, and makes the outage visible as itself. Changes: - Track the arrival time of every current-sensor publish and declare the reading stale after current_timeout (default 30s). Add a current_stale_binary_sensor so the real fault is visible as itself. - While stale: hold motor_running_ rather than recomputing it from a frozen value, suppress no_current (a silent sensor supports no claim about the pump), and stop sampling for anomalies. - On recovery, clear the debounce streak and the spread estimate so the step change back to live data cannot trip the variance detector, and discard the inrush peak of any run whose startup window contained a gap. - Measure runtime from the flow sensor whenever one is configured, falling back to current and then to the output command. Moving water is what the schedule is actually buying, and flow stays valid through a current-sensor outage. - Split "a new run started" from "runtime is accumulating". The anomaly startup window must stay anchored to electrical turn-on, since flow lags the motor by long enough to miss the inrush peak entirely. turned_on_ms_ is now 0 until a sensor confirms the motor, which also stops a stale recovery from restarting the window mid-run and recording steady-state current as inrush. - Document the local ESP-IDF toolchain pitfalls in CLAUDE.md, and stop the commit_pr command pointing at the upstream esphome PR workflow. Verified with esphome compile on an ESP32-S3 build of pool.yaml: clean, no warnings from any touched file. Co-Authored-By: Claude <noreply@anthropic.com>
This file contains hidden or bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Sign up for free
to join this conversation on GitHub.
Already have an account?
Sign in to comment
Add this suggestion to a batch that can be applied as a single commit.This suggestion is invalid because no changes were made to the code.Suggestions cannot be applied while the pull request is closed.Suggestions cannot be applied while viewing a subset of changes.Only one suggestion per line can be applied in a batch.Add this suggestion to a batch that can be applied as a single commit.Applying suggestions on deleted lines is not supported.You must change the existing code in this line in order to create a valid suggestion.Outdated suggestions cannot be applied.This suggestion has been applied or marked resolved.Suggestions cannot be applied from pending reviews.Suggestions cannot be applied on multi-line comments.Suggestions cannot be applied while the pull request is queued to merge.Suggestion cannot be applied right now. Please check back later.
An ESPHome sensor keeps serving its last value indefinitely once its source stops responding, and nothing downstream can tell the difference between that and a real measurement. On two consecutive mornings the PZEM stopped returning valid Modbus frames for exactly the hour both pumps ran, 04:00–05:00, and because its readings froze rather than disappearing, every consumer believed them.
Pump No Currentturned on at 04:00:01 and stayed on for the full hour while the pump was actually drawing ~1500 W. Runtime stopped accumulating for a pump that was running. When frames returned at 05:00:02 the current sensor stepped from a frozen value to a live one in a single sample, which spiked the spread estimate past the variance threshold and setPump Anomaly Statuschattering — 285 transitions, reasonVARIANCE_SPIKE. The energy sensors appearing to dump a whole hour of consumption at once had the same cause: the meter had been counting internally the entire time, only the reads were dead.binary_sensor.pool_statusnever leftonand the recorder was healthy throughout, so this was neither an API drop nor a database problem. The only signal that could have distinguished a live reading from a frozen one was when it last arrived, and nothing was tracking that.This does not fix the underlying dropout, which is still unexplained and most likely electrical — it recovers the instant the cleaner stops, so the cleaner's booster pump is the prime suspect. What this does is stop the controller drawing false conclusions from dead data, and make the outage visible as itself in history.
Changes:
current_sensorpublish and declare the reading stale aftercurrent_timeout(new, default30s). Addcurrent_stale_binary_sensorso a dead sensor is reported as a dead sensor rather than as a pump fault.motor_running_instead of recomputing it from a frozen value, suppressno_current(a sensor that stopped publishing supports no claim about the pump), and stop sampling for anomalies.flow_sensorwhenever one is configured, falling back tocurrent_sensorand then to the output command. Moving water is what the schedule is actually buying, and flow stays valid through a current-sensor outage — in this incident the flow inputs are on the PCF8574 and were live all hour.track_runtime(). The anomaly startup window has to stay anchored to electrical turn-on, because flow lags the motor by long enough to miss the inrush peak the startup check exists to measure.turned_on_ms_is now0until a sensor confirms the motor, which also prevents a stale recovery from restarting the startup window mid-run and recording steady-state current as if it were inrush.CLAUDE.md, and stop thecommit_prcommand delegating to thepr-workflowskill, which belongs to the upstreamesphome/esphomecheckout and would target the wrong repository.No behaviour changes on upgrade beyond the above; nothing persisted is discarded. Both new options are optional with defaults, so existing configs need no edits.
Verified with
esphome compileon an ESP32-S3 build ofpool.yaml— clean, exit 0, no warnings from any touched file.