Depends on #768. This branch is stacked on it, so until #768 merges the diff also shows that commit. Review only the last commit, feat(dist): map the Schneider Electric ADMS extension of CIM16.

Summary

A Schneider Electric ADMS exports an LV network as a header-less CIM16 document with its own extension namespace, http://www.schneider-electric-dms.com/CIM16v33/2017/extension. Customers, generation, and voltage levels are stated only through extension properties, and the export leaves out the source. With #768 alone, such a network reads with its wiring and layout but no loads, generation, or supply.

The new powerio-dist/src/cim/read/sedms.rs maps the extension into MulticonductorNetwork, so the network converts to every distribution format through the shared writers. No writer changes.

Extension Model
UsagePoint at a ServiceLocation (sedms:ServiceLocation.Terminal, .phases; sedms:UsagePoint.p, .q) one load per usage point, its powers shared evenly over the location's phases: wye or single phase with the neutral, delta or phase to phase without it
FlexibleLoad (sedms:FlexibleLoad.Customer, pMax, pAvg, dispatchable, resourceType) an inverter based resource at the customer's location. One that is not dispatchable holds pAvg at unity power factor
ConnectivityNode with sedms:ConnectivityNode.stitchingInfo, when no EnergySource exists a sourcebus joined through closed switches to the stitched nodes, with an ideal source at their sedms:ConductingEquipment.ratedVoltage
Diagram Layout service location points for nodes no equipment places; sedms:Diagram.type GIS as projected coordinates; the supply busbar at the centroid of the nodes it feeds
  • Gating. The mapping runs only when a document uses the extension namespace (xml.rs gives those properties the sedms: prefix by URI). Without it, ServiceLocation and UsagePoint stay unmapped classes, as in feat(dist): read CIM16 LV feeders with text enumerations and a Diagram Layout #768.
  • Findings. Every value the extension fills in is a READ.CIM_DIST.* finding.
  • Reader hooks. read.rs gains a wye_source helper, shared by EnergySource and the placed supply, and a terminal_usage helper. It also gains IBRs and supply busbars in the bus derivation.

Tests

powerio-dist/tests/cim.rs adds a synthetic feeder in the export's form, with invented names, values, and coordinates. No fixture files are added. The tests pin:

  • the mapping: loads, the IBR, the supply, and findings;

  • the layout;

  • the conversion to OpenDSS, PMD, BMOPF, and CIM: each output reparses with its source, loads, and 50 Hz, and the CIM rewrite is byte stable.

  • cargo test: 3408 passed, 0 failed.

  • cargo clippy -p powerio-dist --all-targets --all-features -- -D warnings: clean.

…m Layout

A CIM16 LV feeder stated with sequence impedances and no per phase class
routed to the CGMES reader and failed, and read with an explicit
`cim-dist` token it gave three phase switches for its single phase fuses.

- Route a header-less CIM document with the IEC 61968 customer classes
  (`ServiceLocation`, `UsagePoint`) to `cim-dist`.
- Read an enumeration stated as text (`<cim:Terminal.phases>A</...>`)
  like a reference.
- Take a segment's ampacity from the `WireInfo.ratedCurrent` its
  `AssetDatasheet` names.
- Read the Diagram Layout: a segment's `DiagramObjectPoint`s are its
  route, and a bus takes the end of the first segment at its node, else
  the point of the equipment there or of the composite switch that holds
  a switch. A diagram that names an `EPSG:` code sets the network's
  coordinate reference system.
- Default a CIM16 document set without a `BaseFrequency` to 50 Hz, as the
  CGMES reader does.
- Report `Circuit`, `CompositeSwitch`, and `PSRType` as context.

The new tests pin a synthetic CIM16 feeder: its mapping, its layout, and
its conversion to OpenDSS, PMD, BMOPF, and a byte stable CIM rewrite.
A Schneider Electric ADMS exports an LV network as a header-less CIM16
document with its own extension namespace
(`http://www.schneider-electric-dms.com/CIM16v33/2017/extension`). Its
customers and generation are stated only through extension properties, and
it leaves out the source, so the standard CIM16 mapping reads such a
network with no loads, no generation, and no supply.

The new `cim/read/sedms.rs` module maps the extension into the
multiconductor model, so the network converts to every distribution
format through the shared writers:

- a load per `UsagePoint` at the bus of the terminal its `ServiceLocation`
  is served from, on the location's phases, with the stated `p` and `q`;
- an inverter based resource per `FlexibleLoad`, at its customer's
  location, holding its average output when it is not dispatchable;
- when the documents define no `EnergySource`, a busbar joined through
  closed switches to the nodes `sedms:ConnectivityNode.stitchingInfo`
  marks, with an ideal source at their rated voltage;
- in the Diagram Layout, service location points for nodes no equipment
  places, a GIS diagram as projected coordinates, and the supply busbar at
  the centroid of the nodes it feeds.

The reader applies the mapping only when a document uses the extension
namespace, and every value it fills in is a `READ.CIM_DIST.*` finding. The
new tests pin a synthetic feeder in the export's form: its mapping, its
layout, and its conversion to OpenDSS, PMD, BMOPF, and a byte stable CIM
rewrite.
@MohamedNumair

MohamedNumair commented Oct 29, 2026 •

Copy link
Copy Markdown
Collaborator Author

The two failing checks on this PR come from main, not from this change. validate fails the same way on #766 and #767. #744 fixes both, and both checks pass on that PR.

This PR does not touch the PMD fixtures, the BMOPF writer or powerio-capi. Once #744 merges I will merge main into this branch to rerun the checks.

A diagram's EPSG code other than 4326 no longer reads as projected on that
alone. Widely used geographic codes such as EPSG:4258 read as longitude and
latitude, so the PMD writer keeps their coordinates. Any other code is
projected when a coordinate lies outside the range of degrees; otherwise the
space stays undeclared with a finding naming the code.

A ConnectivityNode or Terminal drawing now gives its bus a location, ahead of
those derived from equipment. Diagram objects and points are consumed only
once their coordinates reach the network, so any other drawing is reported
unmapped instead of disappearing.
A negative, zero, non-finite, or unparsable WireInfo.ratedCurrent read as an
absent rating with no finding. It now draws a VALUE_UNSUPPORTED finding, once
per catalog entry, while an absent rating stays silent.
Service location drawings count as carried once they reach a node, under the
reader's rule that a drawing placing nothing is reported. A sedms GIS diagram
that names no CRS stays projected.
@samtalki samtalki mentioned this pull request Nov 7, 2026
@MohamedNumair
MohamedNumair requested a balanced review from Copilot and removed request for samtalki November 10, 2026 18:06

Copilot AI left a comment

Copy link
Copy Markdown

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

🟡 Changes recommended

Active findings identify unintended electrical connections, incomplete supply energization, incorrect namespace activation, and lost customer demand or generation.

5 open issues
What changed in this PR

Adds Schneider Electric ADMS CIM16 support to the distribution reader, building on #768’s feeder support. The extension maps into MulticonductorNetwork, reusing existing format writers.

Changes:

  • Maps customer demand, flexible generation, and inferred supplies.
  • Adds extension namespace handling and service-location layout support.
  • Documents the supported profile and adds synthetic mapping, layout, and conversion tests.
File Description
README.md Advertises CIM16 ADMS input support.
powerio/​src/​lib.rs Clarifies the routing comment for customer classes.
powerio-dist/​tests/​cim.rs Adds synthetic CIM16 and ADMS regression tests.
powerio-dist/​src/​cim/​xml.rs Normalizes Schneider extension property names.
powerio-dist/​src/​cim/​read/​sedms.rs Implements customer, generation, supply, and layout mapping.
powerio-dist/​src/​cim/​read.rs Integrates extension data and shared reader helpers.
powerio-dist/​src/​cim/​mod.rs Adds customer-class routing markers from #768.
powerio-dist/​README.md Describes ADMS reader support.
docs/​src/​format-fidelity.md Documents customer-class routing from #768.
docs/​src/​distribution.md Explains extension mappings, assumptions, and limitations.
CHANGELOG.md Records ADMS support and the underlying CIM16 changes.

Review effort: Balanced

Comment on lines +60 to +63
doc.objects
.iter()
.flat_map(|object| &object.props)
.any(|(key, _)| key.starts_with("sedms:"))
Comment on lines +383 to +387
let circuits = self
.store
.text(&node, "sedms:ConnectivityNode.connectedCircuits")
.map_or_else(String::new, |c| c.trim().to_owned());
match groups.iter_mut().find(|(c, _, _)| *c == circuits) {
Comment on lines +424 to +425
if let Some(stated) = self.terminal_phases(terminal) {
phases.extend(stated);
}
};
let neutral = map.iter().any(|t| t == "4");
let phases: Vec<String> = map.into_iter().filter(|t| t != "4").collect();
Comment on lines +255 to +274
let n = point.phases.len();
let (topology, map) = match (n, point.neutral) {
(1, _) => (
IbrTopology::SinglePhase,
with_neutral(point.phases.clone(), Configuration::SinglePhase),
),
(3, false) => (IbrTopology::ThreeLeg, point.phases.clone()),
(3, true) => (
IbrTopology::FourLeg,
with_neutral(point.phases.clone(), Configuration::Wye),
),
_ => {
self.drop_record(
"FlexibleLoad",
&id,
&format!("an inverter on {n} phases has no topology in the model"),
);
continue;
}
};