Documentation-only. Record: documentation/Licensed-TasOpenStudio-Validation-Q4.md; evidence: documentation/evidence/licensed-e2e-20261019/. Validated content: Q4 4ee45fef (SAM_UI), 68eded0 (SAM_Validation), 618db819 (SAM), a34a298d (SAM_Tas), d4216f3 (SAM_OpenStudio). No product, test, tolerance, physics or baseline change.

Results (fresh licensed runs, real SAM Analytical UI, Run Simulation > Both)

Test Tas OpenStudio Comparison Result
box-aperture, embedded weather exit 0, Success exit 0 (E+ 25.1.0) 6/0/10/2, 4 contributing + 6 informational PASS (workflow)
box-aperture, explicit Budapest EPW exit 0 exit 0 6/0/10/2 PASS (workflow)
HungaryHouse (14 spaces), explicit EPW exit 0, crash not reproduced exit 0 48/3/41, 14/14 spaces PASS (workflow)

Reports are byte-identical to benchmark-compare.exe; values and differences are independently rechecked against TSD/TBD/ESO output. There is no time offset between the engines.

Main findings (details and proposed fixes in the record)

  • F1: SAM's EPW writer (SAM.Weather.Query.DataString) writes global horizontal and horizontal IR as 0, and horizontal direct into the DNI column. With embedded weather, Tas simulates without solar gain.
  • F2: per-person outdoor air reaches EnergyPlus Ideal Loads 24 h but not Tas, which has no Ventilation profile and no AHU. This is about 99% of E+ box heating. Removing only that input brings heating to within 11%, with the same peak hour.
  • F3: OpenStudio cooling is total (includes latent), while Tas is sensible.
  • F4/F5 (SAM_Tas): the space peak hour is the raw 1-based Tas index (the 871/872 pair), and space peaks are design-day governed rather than annual. Not patched: SAM_Tas is read-only while the HVAC conversion is in progress.
  • F6/F7: a zero-peak hour is reported as 0, and the canonical hash includes UI-only ParameterSet GUIDs.
  • Local build: the local SAM_UI\build has a stale deps.json from the pre-Simulate > OpenStudio Simulation: minimal OpenStudio/EnergyPlus run from SAM_UI (#229) #237 baseline build, so Both/OpenStudio cannot load there. A Rebuild is needed. This is not a product defect.

Unresolved: the box cooling residual (~20%) after aligning ventilation, and the remaining HungaryHouse heating gap (whole-house temperature and internal gains; see F8/C6).

  • F8 / C6 (new, 19 Oct, head 0a569236): HungaryHouse GF_08 heating is mostly Tas window opening (zdwno Part O aperture function, not converted by SAM_OpenStudio). Tas-only experiment: baseline re-run reproduces the original TSD bit-for-bit; closing only GF_08's window gives GF_08 1425.6 → 387.6 kWh and whole-building 4507.4 → 3388.9 kWh (−1118.5 kWh, 40.6% of the 2756 kWh gap). The Air-panel hypothesis is refuted for the bathrooms.

Checks: git diff --check clean; docs/evidence only (4 analysis .cs tools with SPDX headers, not part of any project). Full runs are machine-local under C:\TasOut\licensed-e2e-20261019.

Not for merge without owner review.

  • C7 (new, 19 Oct): all-window Tas sensitivity: heating 4507.4 → 3190.5 kWh (−1317.0, 47.8% of the 2756 kWh gap; GF_08 alone 40.6%, the six other windowed zones +7.2%); 1439.3 kWh remains vs E+. Part O audit: one zdwno,0,22,24,99 string on all 9 windows; GF_08's ramp starts below its 24 °C setpoint; string has one field fewer than EDSL documents; Unrestricted night opening is a loader default. Recommended milestone: ZoneVentilation:WindandStackOpenArea + EMS (design only, nothing implemented).

🤖 Generated with Claude Code

michaldengusiak and others added 2 commits October 19, 2026 08:50
…iagnosis

Fresh licensed Run Simulation > Both runs from the real SAM Analytical UI
(isolated Q4 build): box-aperture with embedded weather and with the source
Budapest EPW, and HungaryHouse (Tas crash not reproduced). Reports
reproduced byte-for-byte by benchmark-compare; values and arithmetic
checked independently against TSD/TBD/ESO output.

Diagnosis: the embedded-weather EPW export has GHI=0 and horizontal
direct in the DNI column (Tas runs without solar); outdoor-air
ventilation reaches EnergyPlus but not Tas; OpenStudio cooling is total
vs Tas sensible; Tas space peak hour is 1-based and space peaks are
design-day governed. No time offset between engines. No product change.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
…anel hypothesis (SAM_UI#239)

Tas-only controlled experiment: baseline re-run reproduces the original TSD bit-for-bit;
closing only GF_08's window (shared aperture type isolated) cuts GF_08 heating 1425.6 -> 387.6 kWh
and whole-building heating 4507.4 -> 3388.9 kWh. Evidence and tools under window-opening/.
No product, test, tolerance or baseline change.

Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com>
michaldengusiak and others added 3 commits October 19, 2026 10:57
…ouse (SAM_UI#239)

Tas-only: detaching all window aperture types cuts heating 4507.4 -> 3190.5 kWh
(-1317.0, 47.8% of the 2756 kWh gap; 1439.3 kWh remains vs E+). Adds aperture
inventory, baseline aperture behaviour, three-scenario comparison, Part O audit and
a window-control architecture assessment. Fixes the earlier dump tool's zone index
(LivingRoom was omitted). No product, test, tolerance or baseline change.

Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com>
Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com>
…ds reconciliation (SAM_UI#239)

GF_08 WindandStackOpenArea + EMS ramp/Part O latch verified in native outputs;
unlimited Ideal Loads run away, capacity-limited variants compared with Tas
(flow character, heating, temperature). 44.6 kWh difference resolved as the
heating design day in an earlier per-zone summary. Corrects C7 per-zone E+ values.
Authored-vs-default audit of the Part O settings. No product change.

Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com>
Pre-F1 embedded-weather evidence superseded by SAM#212; C6-C8 and
engine-physics work frozen (Phase C); findings mapped to roadmap tasks
(SAM#213). All licensed-run evidence kept unchanged.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
@michaldengusiak
michaldengusiak merged commit d5aa34b into sow/2026-Q4 Oct 19, 2026
2 checks passed
@michaldengusiak
michaldengusiak deleted the validation/licensed-tas-openstudio-e2e-q4 branch October 19, 2026 15:13
michaldengusiak added a commit that referenced this pull request Oct 19, 2026
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment

Labels

None yet

Projects

None yet

Development

Successfully merging this pull request may close these issues.

1 participant